Inverter Centralizzati - APV 20k-T/25k-TL

The Radius 20k/25k guarantees operation at the full power rating up to ambient temperatures of 50°C and a voltage range of up to 1000 Vdc.
This latest generation inverter complies with the most stringent EMC requirements (Class B).

The Radius 20k/25k is available in the cabinet version with integrated isolation transformer, anti-islanding protection and overload switch.
This means the AC panel could not be installed downstream of the inverter.

With a maximum operating voltage of 1000 Vdc this solution achieves considerable savings in terms of wiring and allows several modules to be connected to each string, thus reducing the number of strings.

This also results in less power loss, further enhancing the efficiency of these high-performance RADIUS inverters.

Grid connection certifications

Italy: CEI 0-21, ANNEX A70 TERNA; Germany: DIN V VDE V 0126 (VDE V 0126-1-1):2006-02, VDE-AR-N 4105, BDEW; France, Turkey, Greece, Czech Republic: DIN V VDE V 0126-1-1 (VDE V 0126-1-1):2006-02; Spain: P.O. 12.3, RD 661/2007, RD 1565/2010, RD 1663:2000, RD 1699/2011; UK: G59/1:1991, G59/2:1991; Belgium: C10/11:2006; Israel: AS 4777.2:2005, AS 4777.3:2005; South Africa: South African Grid code.

Choose language:
  APV20k-T-E
(EMEA)
APV25k-TL-E
(EMEA)
APV25k-TL-RP
(EMEA)
DC INPUT
MPPT voltage range Udc [V] 465...850 483...850
Minimum operating voltage Udc min [V] 465 450
Maximum voltage allowed Udc max [V] 1,000 (2) 1,000 (2)
Maximum current allowed Idc max [A] 43 51
AC OUTPUT
Rated active power   [kW] 20 25 25 (1)
Rated Output voltage Uac [V] 400 (±15%) 290
Maximum current Iac max [A] 28.9 50
Short circuit current (=1.5*In) Isc [A] 43.3 75
Grid frequency fac [Hz] 50
Harmonic distortion THD grid [%] ≤ 3
Power factor (settable) cosphi   0.99 0.99 from 0.9 inductive to 0.9 capacitive
EFFICIENCY RATING
Maximum efficiency (3)   [%] 95.8 97.6
European efficiency (Euro-ETA) (3)   [%] 94.17 96.9
GENERAL DATA
Protection class     IP33 IP33 IP33
Power switch on AC side
  yes no no
Power switch on DC side     yes yes yes
Reverse polarity protection diodes
on DC side
    yes yes yes
Ground fault monitoring     optional optional optional
Overcurrent protection AC side   yes yes yes
DC side   no no no
Overvoltage protection
AC side   no no no
DC side   optional optional optional
Remote plant monitoring     optional optional optional
Ground kit     optional (2) optional (2) optional (2)
Ambient temperature range
(without power derating)
  [°C] from -10 °C to + 50 °C
Requested air flow (input)   [m3/h] 1,200
Cooling     Thermostatically-controlled
Relative humidity of air   [%] from 5% to 85% without condensation
Maximum altitude   [m] 1,000 m  (2,000 m with derating)
Topology     With isolation transformer Without transformer
Dimensions:
Width x Height x Depth
  mm [inches] 800 x 1,600 x 600 [31.5 x 62.99 x 23.62]
Weight   kg [lbs] 350 [772] 230 [507]
Certification     CE; VDE V 0126-1-1; VDE-AR-N 4105; RD 1663; G59/1; G59/2; C10/11; AS 4777.2; AS 4777.3. CE; BDEW; RD 1565/2010, P.O. 12.3.
(1) Active power with cosphi 0.9 inductive = 22.5 kW, Active power with cosphi 0.9 capacitive = 21.3 kW.
(2) For string configurations, maximum recommended Vdc voltage 965V.  If using the ground kit, maximum Vdc = 900V.
(3) Efficiency refers to values calculated at 500 Vdc (at 25°C), excluding auxiliary power supply.