Inverter Industrial - APV 20k/25k-TL

The Radius 20k/25k guarantees operation at the full power rating up to ambient temperatures of 50°C and a voltage range of up to 1000 Vdc.
This latest generation inverter complies with the most stringent EMC requirements (Class B).

The Radius 20k/25k is available in the cabinet version with integrated isolation transformer, anti-islanding protection and overload switch.
This means the AC panel could not be installed downstream of the inverter.

With a maximum operating voltage of 1000 Vdc this solution achieves considerable savings in terms of wiring and allows several modules to be connected to each string, thus reducing the number of strings.

This also results in less power loss, further enhancing the efficiency of these high-performance RADIUS inverters.

Grid connection certifications
Italy: DK5940; Germany, France, Turkey, Greece and Czech Republic: DIN V VDE V 0126-1-1 (VDE V 0126-1-1):2006-02; Spain: RD 1663:2000; UK: G59/1:1991, G59/2:1991; Belgium: C10/11:2006; Israel AS 4777.2:2005, AS 4777.3:2005.

Contact usFor more information
Choose language:
  APV20k-T APV25k-TL
DC INPUT
Recommended maximum PV power Pdc, max [kW] 23.5 (1) 29 (1)
MPPT voltage range Udc [V] 465...850 483...850
Minimum operating voltage Udc min [V]
465 483
Maximum voltage allowed Udc max [V] 1,000 (2) 1,000 (2)
Maximum current allowed Idc max [A 43 51
AC OUTPUT
Power rating Pac nom [kW] 20 25 (3)
Rated Output voltage Uac [V] 400 (±15%) 290 (4)
Current rating Iac nom [A] 28.9 50
Short circuit current (=1.5*In) Isc [A] 43.3 75
Grid frequency fac [Hz] 50 50
Harmonic distortion THD grid
[%] ≤ 3 ≤ 3
Power factor cosphi   0.99 0.99
EFFICIENCY RATING
Maximum efficiency   [%] 96.71 98.12
European efficiency (Euro-ETA)
[5, 10, 20, 30, 50, 75, 100% of Pac nom]
  [%] 96.01 (5)
[89.7; 93.92; 95.99; 96.54; 96.71; 96.45; 95.93]
97.4 (5)
[90.27; 95.11; 97.51; 97.91; 98.12; 97.74; 97.13]
GENERAL DATA
Protection class     IP33
IP33
Power switch on AC side
  yes no
Power switch on DC side     yes yes
Reverse polarity protection diodes
on DC side
    yes yes
Ground fault monitoring     optional optional
Overcurrent protection AC side   yes yes
DC side   no no
Overvoltage protection
AC side
  no no
DC side   optional optional
Remote plant monitoring     optional optional
Ground kit     optional(2) optional(2)
Ambient temperature range
(without power derating)
  [°C] from -10 °C to + 50 °C from -10 °C to + 50 °C
Requested air flow (input)   [m3/h] 1,200 1,200
Cooling     Thermostatically-controlled Thermostatically-controlled
Relative humidity of air   [%] from 5% to 85% without condensation from 5% to 85% without condensation
Maximum altitude   [m] 1,000 m
(2,000 m with derating)
1,000 m
(2,000 m with derating)
Topology     With isolation transformer Without transformer
Dimensions:
Width x Height x Depth
  mm [inches] 800 x 1,600 x 600 [31.5 x 62.99 x 23.62]
Peso   [kg] 350 [772] 230 [507]
(1) The recommended maximum power of the PV field is usually calculated considering a correction factor of 0.85: PDC max = PAC nom / 0.85. The correction factor may however vary, depending on the geographical location, ambient temperature and type of installation.(2) For string configurations, maximum recommended Vdc voltage 965V. If using the ground kit, maximum Vdc = 900V. (3) At 290V. (4) The acceptable range for the inverter output voltage is 270...400V (-15% +10%). This can be configured in the field on request. For each particular case the output voltage must be selected at the design stage, from within the accepted range. (5) Refers to the DC/AC conversion part, excluding auxiliary power supply.