The Radius 20k/25k guarantees operation at the full power rating up to ambient temperatures of 50°C and a voltage range of up to 1000 Vdc.
This latest generation inverter complies with the most stringent EMC requirements (Class B).
The Radius 20k/25k is available in the cabinet version with integrated isolation transformer, anti-islanding protection and overload switch.
This means the AC panel could not be installed downstream of the inverter.
With a maximum operating voltage of 1000 Vdc this solution achieves considerable savings in terms of wiring and allows several modules to be connected to each string, thus reducing the number of strings.
This also results in less power loss, further enhancing the efficiency of these high-performance RADIUS inverters.
Grid connection certifications
Italy: DK5940; Germany, France, Turkey, Greece and Czech Republic: DIN V VDE V 0126-1-1 (VDE V 0126-1-1):2006-02; Spain: RD 1663:2000; UK: G59/1:1991, G59/2:1991; Belgium: C10/11:2006; Israel AS 4777.2:2005, AS 4777.3:2005.
| APV20k-T | APV25k-TL | |||
| DC INPUT | ||||
| Recommended maximum PV power | Pdc, max | [kW] | 23.5 (1) | 29 (1) |
| MPPT voltage range | Udc | [V] | 465...850 | 483...850 |
| Minimum operating voltage | Udc min | [V] |
465 | 483 |
| Maximum voltage allowed | Udc max | [V] | 1,000 (2) | 1,000 (2) |
| Maximum current allowed | Idc max | [A | 43 | 51 |
| AC OUTPUT | ||||
| Power rating | Pac nom | [kW] | 20 | 25 (3) |
| Rated Output voltage | Uac | [V] | 400 (±15%) | 290 (4) |
| Current rating | Iac nom | [A] | 28.9 | 50 |
| Short circuit current (=1.5*In) | Isc | [A] | 43.3 | 75 |
| Grid frequency | fac | [Hz] | 50 | 50 |
| Harmonic distortion | THD grid |
[%] | ≤ 3 | ≤ 3 |
| Power factor | cosphi | 0.99 | 0.99 | |
| EFFICIENCY RATING | ||||
| Maximum efficiency | [%] | 96.71 | 98.12 | |
| European efficiency (Euro-ETA) [5, 10, 20, 30, 50, 75, 100% of Pac nom] |
[%] | 96.01 (5) [89.7; 93.92; 95.99; 96.54; 96.71; 96.45; 95.93] |
97.4 (5) [90.27; 95.11; 97.51; 97.91; 98.12; 97.74; 97.13] |
|
| GENERAL DATA | ||||
| Protection class | IP33 |
IP33 | ||
| Power switch on AC side | yes | no | ||
| Power switch on DC side | yes | yes | ||
| Reverse polarity protection diodes on DC side |
yes | yes | ||
| Ground fault monitoring | optional | optional | ||
| Overcurrent protection | AC side | yes | yes | |
| DC side | no | no | ||
| Overvoltage protection |
AC side |
no | no | |
| DC side | optional | optional | ||
| Remote plant monitoring | optional | optional | ||
| Ground kit | optional(2) | optional(2) | ||
| Ambient temperature range (without power derating) |
[°C] | from -10 °C to + 50 °C | from -10 °C to + 50 °C | |
| Requested air flow (input) | [m3/h] | 1,200 | 1,200 | |
| Cooling | Thermostatically-controlled | Thermostatically-controlled | ||
| Relative humidity of air | [%] | from 5% to 85% without condensation | from 5% to 85% without condensation | |
| Maximum altitude | [m] | 1,000 m (2,000 m with derating) |
1,000 m (2,000 m with derating) |
|
| Topology | With isolation transformer | Without transformer | ||
| Dimensions: Width x Height x Depth |
mm [inches] | 800 x 1,600 x 600 [31.5 x 62.99 x 23.62] | ||
| Peso | [kg] | 350 [772] | 230 [507] | |
| (1) The recommended maximum power of the PV field is usually calculated considering a correction factor of 0.85: PDC max = PAC nom / 0.85. The correction factor may however vary, depending on the geographical location, ambient temperature and type of installation.(2) For string configurations, maximum recommended Vdc voltage 965V. If using the ground kit, maximum Vdc = 900V. (3) At 290V. (4) The acceptable range for the inverter output voltage is 270...400V (-15% +10%). This can be configured in the field on request. For each particular case the output voltage must be selected at the design stage, from within the accepted range. (5) Refers to the DC/AC conversion part, excluding auxiliary power supply. |