WorldWide (International)

APV System 900p

PRINT
System - Soluzioni in Container - APV System 900p

Plug&play installation
The cabinet structure is easy to transport and install directly at the site. This avoids the need for on-site assembly and makes installation much quicker.

Cost reduction
This solution is designed to guarantee maximum energy efficiency without the need for air conditioning with outside temperatures of up to 50C. Air-conditioned cabinets are however available upon request. These include a specific air conditioning unit for each inverter and are recommended when installed in particularly hot places to prevent power limitations due to eternal overtemperatures. Air conditioning
functions include: free cooling, cooling, anti-condensation.

Modularity and flexibility
A modular solution with possible power upgrades up to a maximum of four 330 kW inverters. Optional accessories are also available to configure systems to meet the full range of customer requirements.

Accessibility
Cabinets are supplied as turnkey solutions and are specifically designed to ensure access to all internal components and inverters, to facilitate inspection and servicing.

Choose language:
DC INPUT
Recommended maximum PV power Pdc, max [kWp] 900
Maximum voltage allowed (*) Udc max [V] 1,000
MPPT voltage range Udc [V] 483...850
Maximum current allowed Idc max [A] 1,593
INTERNAL COMPOSITION
Inverters   3xAPV250k-TL
LV distribution panel   yes
MV transformer   yes
MV cell   yes
LV auxiliaries panel   yes
MV transformer and MV panel
Type of MV transformer   Low loss resin transformer
Transformer power rating
(number secondary windings)
Pac nom
[kVA]
1,200
(triple secondary winding)
Transformer cooling   AN
Transformation ratio [kV] ±2 x 2.5%
(15kV/0.29kV-0.29kV-0.29kV)
Vector group   Dy11y11y11
Transformer no-load loss [W] 1,900
Transformer short-circuit loss (75°C) [W] 12,500
MV panel   gas SF6 insulation as per IEC 62271-200;
Type: 8DH10 24kV 16kA/ 630A;
1 transformer protection,
1 busbar riser
Auxiliary transformer
Standard / Optional   Optional
Type   open frame in metal box
Power rating
(Power rating with air conditioning)
Pac nom
[kVA]
6 (20)
Cooling   AN
Transformation ratio [V] 290-320/400
Vector group   Dyn11
Mechanical Characteristics
Cabinet outside dimensions
(without air conditioning system)
(LxHxD)
[mm]
12,192x2,896x2,438
Overall weight
(without air conditioning system)
[t] 17
Cabinet outside dimensions
(with air conditioning system)
(LxHxD)
[mm]
12,192x2,896x3,338
Overall weight
(with air conditioning system)
[t] 17.9
DETAILS OF CABINET
Structural material   Steel
Windows, doors and frame   External doors in steel.
Transformer room door with Arel lock.
Panel/inverter room back door.
Fully opening door on short side.
Ventilation grilles with G3 filter
Lighting   Ceiling lamp with 2x36 W
fluorescent tubes (panel/inverter room);
Ceiling lamp with 2x36 W
fluorescent tubes (transformer room);
Emergency ceiling lamp
UPS   yes, single-phase, 1kVA, 5 min.
(*)For string configurations, maximum recommended Vdc voltage = 965V. With ground kit maximum Vdc voltage = 900V.