Ideal for on-roof systems. The fully customisable ROOF cabinet can be used with Radius inverters from 20 to 110 kW with or without transformer according to customer specifications.
| APV SYS-R 150p | APV SYS-R 260p | |||
| DC INPUT | ||||
| Maximum voltage allowed(1) | Udc max | [V] | 1,000 | 1,000 |
| MPPT voltage range | Udc | [V] | 488...850 (2) 483...850 (3) |
488...850 (2) 483...850 (3) |
| Maximum current allowed | Idc max | [A] | 268 | 454 |
| CABINET INTERNAL COMPOSITION | ||||
| Inverter | 2xAPV65k-TL | 2xAPV110k-TL | ||
| LV and auxiliaries distribution panel | yes | yes | ||
| LV transformer | yes | yes | ||
| Air filters | yes (not with air-conditioned versions) |
yes (not with air-conditioned versions) |
||
| LV transformer | ||||
| Type of LV transformer | Air-insulated windings | Air-insulated windings | ||
| Transformer power rating (number secondary windings) |
Pac nom [kVA] |
160 (double secondary winding) |
250 (double secondary winding) |
|
| Transformer cooling | AN | AN | ||
| Transformation ratio | [kV] | 0.4kV/0.32kV-0.32kV (2) 0.4kV/0.29kV-0.29kV (3) |
0.4kV/0.32kV-0.32kV (2) 0.4kV/0.29kV-0.29kV (3) |
|
| Vector group | Dy11-y11 | Dy11-y11 | ||
| Transformer no-load loss | [W] | 562.5 | 750 | |
| Transformer short-circuit loss (75°C) | [W] | 2,544.5 | 3,635 | |
| Interface device (ID) | 250 A motorised automatic switch |
400 A motorised automatic switch |
||
| Mechanical Characteristics | ||||
| Cabinet outside dimensions (without air conditioning system) |
(LxHxD) mm [inches] |
3,700 x 2,420 x 1,600 [145.7 * 95.3 * 63] |
3,700 x 2,420 x 1,600 [145.7 * 95.3 * 63] |
|
| Overall weight (without air conditioning system) |
[t] | 2.8 | 3.3 | |
| Cabinet outside dimensions (with air conditioning system) |
(LxHxD) mm [inches] |
3,700 x 2,420 x 2,000 [145.7 * 95.3 * 78.7] |
3,700 x 2,420 x 2,000 [145.7 * 95.3 * 78.7] |
|
| Overall weight (with air conditioning system) |
[t] | 2.9 | 3.5 | |
| DETAILS OF CABINET | ||||
| Structural material | Steel | Steel | ||
| Windows, doors and frame | Self-supporting base – 3 doors on long side and 1 transformer-room door on short side. Ventilation grilles with G3 filter. |
Self-supporting base – 3 doors on long side and 1 transformer-room door on short side. Ventilation grilles with G3 filter. |
||
| Lighting | 3 ceiling lamps with 13 W fluorescent tubes |
3 ceiling lamps with 13 W fluorescent tubes |
||
| UPS | yes, 1KVA single phase | yes, 1KVA single phase | ||
| Grid connection | ||||
| Italy: CEI 0-16; ANNEX A70 TERNA EMEA: BDEW; RD 1565/2010, P.O. 12.3. South Africa: S.A. Grid code. |
||||
| (1) For string configurations, maximum recommended Vdc voltage = 965V. With ground kit maximum Vdc voltage = 900V. (2) APV..k-TL for Italy. (3) APV..k-TL-E for EMEA and APV..k-RP for other countries. |